Step 1: The Beam Is Regulated: Start With the CRC Girder Tables
A bearing wall that is removed must be replaced by a girder and jack studs that carry its load to the foundation. 2025 CRC R502.5 says the allowable spans of girders and headers made of dimension lumber may not exceed the values in Tables R602.7(1), R602.7(2) and R602.7(3). For a bearing wall inside the house use Table R602.7(2), Girder Spans and Header Spans for Interior Bearing Walls; Table R602.7(1) is for exterior bearing walls. Anything the tables do not cover is an engineered element under R301.1.3. Temporary shoring of the floor above while the wall is open is trade practice, not a quoted code rule.
Step 2: Reading Table R602.7(2)
The rows are grouped by what the girder supports (One floor only, Two floors), then by size written as plies, such as 4-2 x 10 (four 2x10s). The columns are building width of 12, 24 or 36 feet, measured perpendicular to the ridge (note c), and each shows the maximum Span in feet-inches and NJ, the number of jack studs required at each end. Spans assume No. 2 grade Douglas fir-larch, hem-fir, Southern pine or spruce-pine-fir (note b). Lumber sizes in the code are nominal unless stated otherwise (R301.8).