HVAC (C-20) · Lesson 4 of 6Condensate Drains: Pipe Size, Slope, and Overflow Protection
"Condensate Drains: Pipe Size, Slope, and Overflow Protection" is lesson 4 of 6 in the HVAC (C-20) Learning Hub. It opens with "Cooling Coils Make Water Every Hour They Run" and works through 5 short steps, then a worked example you can check yourself against.
One-time purchase, no subscription. Law & Business included.
The first steps of this lesson
Step 1: Cooling Coils Make Water Every Hour They Run
An air-conditioning coil removes moisture from the air, and a condensing appliance makes condensate from its exhaust. CMC Section 310.1 requires condensate from air-cooling coils, condensing appliances and similar equipment to be collected and discharged to an approved plumbing fixture or disposal area, and it may not drain over a public way. Where it enters the drainage system it goes through an indirect waste pipe sloped not less than 1/8 inch per foot (1 percent) and made of approved corrosion-resistant material not smaller than the outlet size.
Step 2: Size the Pipe by Tons - CMC Table 310.3
CMC Section 310.3 sizes condensate waste pipes from air-cooling coils by equipment capacity in tons of refrigeration: up to 20 tons = 3/4 in.; 21 to 40 tons = 1 in.; 41 to 90 tons = 1-1/4 in.; 91 to 125 tons = 1-1/2 in.; 126 to 250 tons = 2 in. The sizes apply to one unit or a combination of units, or as the manufacturer recommends. A big commercial unit does NOT get the 3/4 in. pipe you use at a house.
The remaining 3 steps, the worked example and the quiz are in the course. This is a preview. The full lesson, with the step-by-step explanations, a worked example and a quick-check quiz, is inside the classroom.