Step 1: When a Guard Is Required
2025 CBC Section 1015.2 requires guards along open-sided walking surfaces such as mezzanines, equipment platforms, aisles, stairs, ramps and landings that are more than 30 inches above the floor or grade below at any point within 36 inches horizontally of the open side, and at the perimeter of occupiable roofs. 2025 CRC Section R321.1.1 prints the same 30 inch and 36 inch test for houses and adds that insect screening is not a guard. Measure the drop at the worst point, not the average.
Step 2: Guard Height
2025 CBC Section 1015.3 requires guards at least 42 inches high, measured vertically from the adjacent walking surface or, on stairs, from the line connecting the nosings. In Group R-3 and inside Group R-2 dwelling units, guards on the open sides of stairs need only be 34 inches (CBC Section 1015.3 Exception 1 and CRC Section R321.1.2 Exception 1). Where the top of a stair guard also serves as the handrail, it must sit between 34 and 38 inches.
The remaining 3 steps, the worked example and the quiz are in the course. This is a preview. The full lesson, with the step-by-step explanations, a worked example and a quick-check quiz, is inside the classroom.