The first steps of this lesson
Step 1: Steep Roofs Shed Water, Low-Slope Roofs Hold It
A shingle roof sheds water because gravity moves it off quickly. A low-slope roof is a continuous waterproof membrane that has to carry water to a drain, so the slope, the drains, and the membrane all have to work together. Asphalt shingles are not allowed below 2:12 (2025 California Residential Code R905.2.2; 2025 California Building Code 1507.2.2). Below that line the roofer is installing a membrane or other low-slope system, and each system has its own minimum slope for drainage.
Step 2: Minimum Design Slope Depends on the System
Built-up roofs, modified bitumen, single-ply (TPO, EPDM, PVC), sprayed polyurethane foam, and liquid-applied roofs all need a design slope of at least 1/4 unit vertical in 12 horizontal (2 percent) for drainage (CBC 1507.10.1, 1507.11.1, 1507.12.1, 1507.13.1, 1507.14.1; CRC R905.9.1, R905.11.1, R905.12.1, R905.13.1, R905.14.1). The one exception is coal-tar built-up roofing, which may go down to 1/8:12 (1 percent). Metal roof panels are different: lapped, nonsoldered-seam panels need 3:12 without lap sealant or 1/2:12 with applied lap sealant, and standing-seam panels need 1/4:12 (CBC 1507.4.2; CRC R905.10.2).
The remaining 3 steps, the worked example and the quiz are in the course. This is a preview. The full lesson, with the step-by-step explanations, a worked example and a quick-check quiz, is inside the classroom.
Independent exam preparation. Contractors Classroom is not affiliated with the Contractors State License Board, and no course can guarantee a passing result.