Step 1: A Grease Duct Stands Alone
The 2025 California Mechanical Code (CMC) Section 510.1 says ducts shall not pass through fire walls, Section 510.1.1 says all ducts lead directly to the exterior of the building, and Sections 510.1.2 and 510.1.8 say the Type I exhaust system shall not be interconnected with any other building ventilation or exhaust system and must be independent. Listed grease ducts are installed to their listing and the manufacturer instructions (Section 510.4). The rest of this lesson is about the other grease ducts, the field-fabricated sheet metal ducts of Section 510.5.
Step 2: Metal and Welds
Section 510.5.1 requires carbon steel not less than 0.060 inch (No. 16 MSG) or stainless steel not less than 0.048 inch (No. 18 MSG), and the duct must be supported by that same metal. That is thicker than the hood, which only needs 0.048 inch steel (Section 508.3). Section 510.5.3 requires all seams, joints, penetrations, and duct-to-hood collar connections to have a liquid-tight continuous external weld. Butt welded connections are not permitted (Section 510.5.4). For telescoping and bell-type joints the inside section is always uphill of the outside section with an overlap of not more than 2 inches (Section 510.5.5). Bolts, screws, and rivets must not penetrate duct walls (Section 510.1.6), and a leakage test (light test, water pressure test, or approved equivalent per ASHRAE 154) is required before the duct is used or concealed (Section 510.5.6).
The remaining 3 steps, the worked example and the quiz are in the course. This is a preview. The full lesson, with the step-by-step explanations, a worked example and a quick-check quiz, is inside the classroom.
Independent exam preparation. Contractors Classroom is not affiliated with the Contractors State License Board, and no course can guarantee a passing result.