Step 1: What the Energy Code limits
2025 California Energy Code §130.5(c) (nonresidential and hotel/motel buildings): the maximum combined voltage drop on both installed feeder conductors and branch circuit conductors to the farthest connected load or outlet shall not exceed 5 percent. Multifamily buildings carry the same 5 percent limit in §160.6(c). The exception is voltage drop permitted by California Electrical Code Sections 647.4, 695.6 and 695.7. The limit is combined: whatever the feeder uses up leaves less for the branch circuit.
Step 2: Where the wire resistance comes from
2025 CEC Chapter 9, Table 8 "Conductor Properties" prints direct-current resistance at 75°C (167°F) in ohms per kilometer and ohms per 1000 feet (ohm/kFT). For uncoated copper: 14 AWG solid 3.07; 12 AWG solid 1.93; 10 AWG solid 1.21; 8 AWG solid 0.764; and for stranded 6 AWG 0.491, 4 AWG 0.308, 2 AWG 0.194, 1/0 AWG 0.122. Stranded 12, 10 and 8 AWG are slightly higher (1.98, 1.24 and 0.778). Table 8 Note 1 says the values are valid only for the parameters given.