Step 1: What California Prints About Slab Moisture
Flooring that is glued or sealed over a concrete slab is only as dry as the slab beneath it, so the first question is what was built under the concrete. California answers that in 2025 CBC Section 1907.4, 2025 CRC Section R506.3.3 and 2025 CALGreen Section 4.505.2: a vapor retarder and a capillary break. None of these sections prints a relative-humidity or emission-rate limit for the finished floor, so the pass/fail number for the flooring itself is the flooring or adhesive manufacturer's published limit, not a California code number.
Step 2: The Vapor Retarder in the Building Code (CBC 1907.4)
2025 CBC Section 1907.4 requires a 6-mil (0.006 inch; 0.15 mm) polyethylene vapor retarder with joints lapped not less than 6 inches (152 mm), placed between the base course or subgrade and the concrete floor slab, or other approved equivalent methods or materials to retard vapor transmission. Section 1907.3 sets the slab-on-ground thickness at not less than 3 1/2 inches (89 mm). These are the numbers a flooring contractor can check against the plans and the slab inspection record.