The first steps of this lesson
Step 1: The Code Ties Loose-Fill to Weight
Loose-fill insulation is sold by weight, and it fluffs up and later settles, so depth alone cannot prove the R-value. The 2025 California Energy Code says so directly: when loose-fill insulation is installed, the minimum installed weight per square foot shall conform with the insulation manufacturer's installed design weight per square foot at the manufacturer's labeled R-value (Section 150.0(b)). The bag chart on the product is where you find that design weight, so the bag count is a code check, not only a purchasing number.
Step 2: Find the R-Value the Code Requires
For a new single-family ceiling the mandatory floor is a U-factor not over U-0.043, or R-22 or greater for the insulation alone between wood framing; in an alteration, U-0.054 or R-19 (Section 150.0(a)2 and its exception). The prescriptive package is higher: Table 150.1-A, Option C ceiling insulation for vented attics is R-38 in Climate Zone 1 and 8 through 16, and R-30 in Climate Zones 2 through 7 (Option B ceiling insulation is R-38 except R-30 in Zones 3, 5, 6 and 7). Use the R-value on the plans or compliance documents, and remember the attic access door must have permanently attached insulation and be gasketed (150.0(a)3).