The first steps of this lesson
Step 1: Where Anchored Veneer Is Allowed
2025 CRC R703.8 limits anchored stone and masonry veneer over wood or cold-formed steel backing to the first story above grade plane and 5 inches in thickness, with two exceptions that allow more height. Table R703.8(1) covers Seismic Design Categories A, B and C: up to 30 feet above a noncombustible foundation, 5 inches thick and 50 pounds per square foot. Table R703.8(2) covers detached one- and two-family dwellings in D0, D1 and D2: generally 20 feet above the foundation, 4 inches thick and 40 psf (3 inches and 30 psf for D2). These are installed weights including mortar, grout and lath. Veneer carries only its own dead load above openings, on noncombustible lintels with at least 4 inches of bearing (R703.8.3).
Step 2: Tie Size, Embedment and Spacing
Ties are corrosion-resistant metal, embedded in mortar or grout and extending into the veneer at least 1 1/2 inches with at least 5/8 inch of mortar or grout cover to the outside face (R703.8.4). Strand wire ties are not less than No. 9 U.S. gage (0.148 inch) with a hook embedded in the mortar joint; sheet metal ties are not less than No. 22 gage by 7/8 inch corrugated (R703.8.4.1). Each tie supports not more than 2.67 square feet of wall area and is spaced at most 32 inches on center horizontally and 24 inches vertically. In Seismic Design Category D0, D1 or D2, on townhouses in category C, or where wind exceeds 30 psf, each tie supports not more than 2 square feet. Because 32 x 24 inches is 5.33 square feet, the area limit is what really controls the layout.
The remaining 3 steps, the worked example and the quiz are in the course. This is a preview. The full lesson, with the step-by-step explanations, a worked example and a quick-check quiz, is inside the classroom.
Independent exam preparation. Contractors Classroom is not affiliated with the Contractors State License Board, and no course can guarantee a passing result.