Step 1: When This Applies
Chapter 11B of the 2025 California Building Code (CBC) covers public buildings, public accommodations, commercial buildings and public housing. CBC 11B-212.3 requires at least 5 percent, but no fewer than one, of each type of sink in an accessible room to comply with 11B-606, and 11B-213.3.4 requires at least 10 percent, but no fewer than one, of the lavatories to comply. The plans call out which ones. A stock closed sink base is not acceptable at those fixtures, so confirm with the designer before you build boxes.
Step 2: Counter Height Limit
CBC 11B-606.3 requires the front of the higher of the rim or the counter surface to be no more than 34 inches above the finish floor. Exception 2 permits an adjustable-height sink in a residential dwelling unit kitchen, 29 inches minimum to 36 inches maximum, where rough-in plumbing allows connections at 29 inches. A 36-inch counter fails the 34-inch limit by 2 inches.