The first steps of this lesson
Step 1: What the Classes Mean
Low-voltage circuits are grouped by how much power the source can deliver. 8 CCR §2585.1 classifies them: a Class 1 power-limited circuit is supplied from a source rated not more than 30 volts and 1000 volt-amperes; a Class 1 remote control or signaling circuit may run up to 600 volts with no limit on source power; and the source of a Class 2 or Class 3 circuit must be listed equipment marked as a Class 2 or Class 3 power source. Only two exceptions are printed: thermocouples need no Class 2 listing, and a dry cell battery of 30 volts or less (no more capacity than series-connected No. 6 carbon zinc cells) counts as an inherently limited Class 2 source.
Step 2: Marking You Must Be Able to Read
8 CCR §2585.2 requires a Class 2 or Class 3 power supply unit to be durably marked where plainly visible with the class of supply and its electrical rating. 2025 CEC Chapter 9 Tables 11(A) and 11(B) add that a Class 2 source not suitable for wet locations must be marked that way. If the nameplate does not state Class 2 or Class 3, treat it as an ordinary power supply and do not wire it as a Class 2 circuit.