Low Voltage Systems (C-7) · Lesson 1 of 4Voltage Drop on Low-Voltage DC Runs (Locks, Cameras, Sounders)
"Voltage Drop on Low-Voltage DC Runs (Locks, Cameras, Sounders)" is lesson 1 of 4 in the Low Voltage Systems (C-7) Learning Hub. It opens with "Why Low Voltage Has So Little Room to Lose" and works through 5 short steps, then a worked example you can check yourself against.
One-time purchase, no subscription. Law & Business included.
The first steps of this lesson
Step 1: Why Low Voltage Has So Little Room to Lose
Magnetic locks, cameras, strobes and card readers run on 12 or 24 volts, so even a couple of volts lost in the wire is a big share of what the device needs. A 2.4 V drop is 10 percent of a 24 V supply but only 2 percent of a 120 V circuit. Too little voltage means a maglock that holds weakly, a camera that reboots, or a notification appliance that will not sound. The California code books on disk do not print a percentage limit for this drop on a Class 2 circuit. The limit you design to is the minimum operating voltage on the device's own nameplate or installation sheet, and the lesson below uses 24 VDC plus or minus 10 percent as a stated example.
Step 2: Measure the Whole Loop, Not One Way
Direct current has to travel out on one conductor and come back on the other, so the wire that matters is twice the one-way distance. A lock 250 feet from its power supply is a 500-foot circuit. Forgetting to double the distance is the most common voltage-drop mistake and it makes every answer come out half as bad as the real jobsite.
The remaining 3 steps, the worked example and the quiz are in the course. This is a preview. The full lesson, with the step-by-step explanations, a worked example and a quick-check quiz, is inside the classroom.