Step 1: When Panic Hardware Is Mandatory
2025 CBC §1010.2.8 says swinging doors serving a Group H occupancy, and swinging doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy (the section also names assembly areas not classified as assembly occupancies, and I-2 occupancies), shall not be provided with a latch or lock other than panic hardware or fire exit hardware. That is a prohibition on every other kind of latch, not just a requirement to add a bar. The section lists exceptions, for example a main exit of a Group A occupancy may use a key-operated locking device under §1010.2.4, Item 3, and Group A or E doors with panic hardware may be electrically locked under §1010.2.10.
Step 2: Special Rooms That Force Panic Hardware
Two room types are named in the CBC. §1010.2.8.1: a refrigeration machinery room larger than 1,000 square feet needs at least two exit or exit access doorways that swing in the direction of egress travel and have panic hardware or fire exit hardware. §1010.2.8.2: exit or exit access doors serving transformer vaults, battery or energy storage rooms and modular data centers need panic hardware or fire exit hardware, and so do rooms with 800 amperes or more of overcurrent, switching or control equipment where the door is less than 25 feet from the equipment working space. Those doors must swing in the direction of egress travel.
The remaining 3 steps, the worked example and the quiz are in the course. This is a preview. The full lesson, with the step-by-step explanations, a worked example and a quick-check quiz, is inside the classroom.
Independent exam preparation. Contractors Classroom is not affiliated with the Contractors State License Board, and no course can guarantee a passing result.