Step 1: Which Scaffold Section Plasterers Use
Title 8 of the California Code of Regulations (8 CCR) section 1640 covers light-duty wooden pole scaffolds to be used by carpenters, lathers, shinglers, painters, plasterers, sheet metal workers or other trades not using heavy tools or storing heavy materials on the scaffolds. Work that uses heavy tools or stores heavy materials on the deck falls outside this light-duty section. The exterior light-duty rules are in 1640(b), and the interior light-duty rules are in 1640(c).
Step 2: Uprights, Ledgers and Ties
Under 8 CCR 1640(b)(1), for heights not to exceed 20 feet the uprights are 2-inch by 4-inch lumber or heavier, spaced not more than 3 feet between uprights at right angles to the wall and not more than 10 feet center to center parallel to the wall. Uprights on a slippery surface need a continuous sill, and on earth they rest on the equivalent of a 2 x 10 x 10 inch wooden base. Under 1640(b)(2), ledgers spanning not more than 3 feet use two pieces of 1 x 6 board, one on each side of the uprights, single 2 x 4 ledgers are not permitted, and vertical spacing of ribbons and ledgers shall not exceed 7 feet. Under 1640(b)(3), the scaffold is tied to the building with ties not more than 20 feet apart horizontally and vertically.
The remaining 3 steps, the worked example and the quiz are in the course. This is a preview. The full lesson, with the step-by-step explanations, a worked example and a quick-check quiz, is inside the classroom.