The first steps of this lesson
Step 1: What Backflow Actually Is
Backflow is the reversal of normal flow - contaminated water, gas, or suspended solids traveling backward into the clean potable water supply, instead of forward out to where it's supposed to go. It typically happens from either backpressure (something downstream pushes harder than the supply) or backsiphonage (a drop in supply pressure creates suction, pulling water backward). Every backflow device exists to stop one or both of those.
Step 2: Air Gap - the Simplest, Most Reliable Method
An air gap is a physical, open vertical space between a supply outlet and the flood-level rim of a fixture - there's no mechanical part to fail because there's simply no direct connection at all. It's the gold-standard protection for the highest-hazard cross-connections, alongside the RPZ assembly below.
Step 3: AVB and PVB - Vacuum Breakers, for Backsiphonage Only
An Atmospheric Vacuum Breaker (AVB) is the simplest mechanical device - it's approved only where there's no downstream shutoff valve, and it cannot be used under continuous pressure. A Pressure Vacuum Breaker (PVB) improves on that: a single check valve plus an air inlet valve, commonly used for irrigation, and it must be installed at least 12 inches above the highest downstream outlet per CPC 603. Neither AVB nor PVB protects against backpressure - only backsiphonage.
The remaining 2 steps, the worked example and the quiz are in the course. This is a preview. The full lesson, with the step-by-step explanations, a worked example and a quick-check quiz, is inside the classroom.
Independent exam preparation. Contractors Classroom is not affiliated with the Contractors State License Board, and no course can guarantee a passing result.