Warehouse Evaporators: Specific Efficiency, Fan Control and Static Pressure (Energy Code 120.6(a)3)
"Warehouse Evaporators: Specific Efficiency, Fan Control and Static Pressure (Energy Code 120.6(a)3)" is lesson 7 of 8 in the Refrigeration (C-38) Learning Hub. It opens with "Which Evaporators Section 120.6(a)3 Covers" and works through 5 short steps, then a worked example you can check yourself against.
One-time purchase, no subscription. Law & Business included.
Steps in this lesson
Which Evaporators Section 120.6(a)3 Covers
Fan Motors
Variable Speed and Off-Cycle Airflow
Specific Efficiency: Table 120.6-A-2
Static Pressure and the Quick-Chill Exception
The worked example in the course applies this lesson to a realistic job in 5 steps, moving through "Freezer evaporator input limit", "Cooler evaporator input limit", and "Time at reduced airflow".
What you'll be able to do
Explain the main idea of "Warehouse Evaporators: Specific Efficiency, Fan Control and Static Pressure (Energy Code 120.6(a)3)" in plain language you can use on the exam.
Apply this step with confidence: "Specific Efficiency: Table 120.6-A-2".
Apply this step with confidence: "Static Pressure and the Quick-Chill Exception".
Test yourself on the worked example and the quick-check quiz inside the classroom.
The diagram for this lesson, exactly as it appears in the Learning Hub.
The first steps of this lesson
Step 1: Which Evaporators Section 120.6(a)3 Covers
2025 Energy Code Section 120.6(a)3 applies to new fan-powered evaporators used in coolers and freezers of refrigerated warehouses of 3,000 square feet or more (the Section 120.6(a) scope). Smaller refrigerated spaces follow the Title 20 walk-in rules. The section sets motor, fan-control, efficiency and static-pressure requirements, and the fan controls are verified by an acceptance test before an occupancy permit is granted (Section 120.6(a)7B).
Step 2: Fan Motors
Section 120.6(a)3A requires single-phase evaporator fan motors of less than 1 hp and less than 460 volts, in newly installed evaporators, to be electronically commutated motors or to have a minimum motor efficiency of 70 percent when rated per NEMA Standard MG 1-2006 at full load rating conditions.
Step 3: Variable Speed and Off-Cycle Airflow
Evaporator fans served by a suction group with multiple compressors, or by a single compressor with variable capacity, must be variable speed, controlled by space temperature or humidity (Section 120.6(a)3B). Evaporator fans served by a single compressor without variable capacity must use controls that reduce airflow by at least 40 percent for at least 75 percent of the time the compressor is not running (Section 120.6(a)3C). Exceptions cover alterations of less than all evaporators in an existing space, controlled-atmosphere coolers certified by a licensed engineer for constant 100 percent airflow, and quick-chill areas.
The remaining 2 steps, the worked example and the quiz are in the course. This is a preview. The full lesson, with the step-by-step explanations, a worked example and a quick-check quiz, is inside the classroom.